Uniformity of stratum-ventilated thermal environment and thermal sensation

Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review

53 Scopus Citations
View graph of relations

Author(s)

Detail(s)

Original languageEnglish
Pages (from-to)521-532
Journal / PublicationIndoor Air
Volume24
Issue number5
Online published19 Jan 2014
Publication statusPublished - Oct 2014

Abstract

Three human test series were conducted to evaluate the uniformity of the thermal environments in a stratum-ventilated chamber with dimensions of 8.8 m (L) × 5.1 m (W) × 2.4 m (H). In all, nineteen conditions were generated by adjusting the room temperature, supply airflow rate, and supply terminal type. An air diffuser performance index (ADPI) of at least 80% was achieved for most cases. This result shows that the air velocity and temperature in the occupied zone are reasonably uniform. Subjective assessments using the ASHRAE 7-point scale indicate that the thermal sensations of the subjects in stratum ventilation are also uniform. This study examines the applicability of the predicted mean vote (PMV) model for evaluating stratum ventilation. When compared to the actual mean thermal sensation votes (ATS), the PMV values are acceptable. The PMV results at a height of 1.1 m above the floor show better agreement with the ATS than at a height of 0.1 m.

Research Area(s)

  • Air diffusion performance index, Effective draft temperature, Stratum ventilation, Thermal sensation, Uniformity

Citation Format(s)

Uniformity of stratum-ventilated thermal environment and thermal sensation. / Cheng, Y.; Fong, M. L.; Yao, T. et al.
In: Indoor Air, Vol. 24, No. 5, 10.2014, p. 521-532.

Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review