Abstract
The influence of the supply air temperature on the mean local air age and thermal comfort of a typical individual office under stratum ventilation is investigated by a numerical method, which is validated by an experiment carried out by the authors. The results show that for an office, when the supply air temperature is increased from 19 °C to 21 °C, the corresponding mean occupied zone temperature rises from 24.5 °C to 26.5 °C. The inhaled air quality for the occupant is improved when supply air temperature rises from 19 °C to 21 °C. Also, the thermal comfort indices (predicted mean vote or PMV, predicted percentage of dissatisfied or PPD and predicted dissatisfied or PD) fulfill the requirements of ISO 7730 and CR 175 1998. For summer cooling operation, stratum ventilation may offer a feasible solution to elevated indoor temperatures, which are recommended by several governments in East Asia. © 2010 Elsevier Ltd.
| Original language | English |
|---|---|
| Pages (from-to) | 501-510 |
| Journal | Building and Environment |
| Volume | 46 |
| Issue number | 2 |
| DOIs | |
| Publication status | Published - Feb 2011 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
-
SDG 9 Industry, Innovation, and Infrastructure
-
SDG 12 Responsible Consumption and Production
Research Keywords
- Elevated indoor temperatures
- Mean local air age
- Stratum ventilation
- Thermal comfort
Fingerprint
Dive into the research topics of 'The impact of temperature on mean local air age and thermal comfort in a stratum ventilated office'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver