Abstract
This paper investigates the relative stability between nucleate and film boiling modes of FC-72 and HFE-7100, which have potential to electronic device cooling applications. Equilibrium heat flux, qc, which refers to as an index for measuring the relative stability of boiling, was obtained at a liquid subcooling of 0-20 K. Experimental results reveal that (1) qc increases with liquid subcooling; (2) although the FC-72 exhibits a higher critical heat flux (CHF) than does the HFE-7100, somewhat unexpectedly, the equilibrium heat flux for the latter is greater than the former. Restated, at a prescribed heat flux, the risk to burnout for boiling of FC-72 is higher than that of HFE-7100. The shift in boiling curves interprets the experimental findings.
| Original language | English |
|---|---|
| Pages (from-to) | 352-355 |
| Journal | Journal of Thermal Science |
| Volume | 9 |
| Issue number | 4 |
| DOIs | |
| Publication status | Published - 2000 |
| Externally published | Yes |
Bibliographical note
Publication details (e.g. title, author(s), publication statuses and dates) are captured on an “AS IS” and “AS AVAILABLE” basis at the time of record harvesting from the data source. Suggestions for further amendments or supplementary information can be sent to [email protected].Research Keywords
- Boiling
- FC-72
- HFE-7100
- Relative stability
- Subcooling
Fingerprint