Performance analysis and optimization of free cooling strategies for a liquid-cooled data center

Weinan Zhou, Qin Sun*, Weimin Luo, Wei Xiao, Pengfei Cui, Wei Wu, Kaijun Dong

*Corresponding author for this work

Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review

15 Citations (Scopus)

Abstract

The increasing power density of IT electronics and the enormous energy consumption of data centers lead to the urgent demand for efficient cooling technology. Due to its efficiency and safety, liquid-cooled heat sink technology may gradually replace air-cooled technology over time. With the ambient or higher water supply temperature, the liquid-cooled technology shortens the operating time of the chiller and improves its coefficient of performance, while the pump power consumption may increase for satisfying the constant cooling capacity. Therefore, it is significant to study the optimal water supply temperature to achieve energy-efficient operation of data centers. A virtual 30.1 kW data center is considered as the case, the liquid-cooled system is constructed with a combination of innovative manifold microchannel heat sink with oblique fins and indirect evaporative cooling technology to minimize energy consumption. A hybrid thermal management model integrating the heat dissipation model and the power consumption model is established by TRNSYS and FLUENT software. To the highest chip-safe operating temperature premise, the energy performance is analyzed under various water supply temperatures in Guangzhou. The result shows that only 21.5-hour mechanical cooling is needed with the 30 °C server inlet temperature throughout the year. And the minimized power consumption occurs with the constant 29 °C server inlet temperature. Moreover, the temperature adaptive control strategy (TACS) is adopted to test the cooling system power consumption under different regulation frequencies, and the by-week TACS can achieve another 11.5% energy saving than the minimum power consumption of the constant temperature control strategy. © 2023, Tsinghua University Press.
Original languageEnglish
Pages (from-to)1317–1330
JournalBuilding Simulation
Volume16
Issue number8
Online published17 Jul 2023
DOIs
Publication statusPublished - Aug 2023

Research Keywords

  • control strategy
  • data center
  • indirect evaporative cooling
  • liquid cooling system
  • manifold microchannel heat sink

Fingerprint

Dive into the research topics of 'Performance analysis and optimization of free cooling strategies for a liquid-cooled data center'. Together they form a unique fingerprint.

Cite this