Abstract

This paper presents a novel stator single-phase-to-ground fault protection of Powerformer in parallel based on the fuzzy clustering algorithms. First, the direction and magnitude of zero-sequence current and leakage current are analyzed, and four fault characters are selected as historical data. Then the historical data are divided into two groups by fuzzy clustering algorithms, and cluster center of each group is calculated. The space relative distance among detected pattern and two cluster centers is finally calculated to discriminate the faulty Powerformer. Simulation results have shown that, under different fault conditions, the new scheme can distinguish reliably internal faults from external faults, and can detect stator single-phase-to-ground fault occurred in which Powerformer with resistance 5 kΩ. A 100% of the winding can be fully protected. © 2013 Elsevier Ltd. All rights reserved.
Original languageEnglish
Pages (from-to)321-328
JournalInternational Journal of Electrical Power and Energy Systems
Volume53
Issue number1
DOIs
Publication statusPublished - 2013
Externally publishedYes

Bibliographical note

Publication details (e.g. title, author(s), publication statuses and dates) are captured on an “AS IS” and “AS AVAILABLE” basis at the time of record harvesting from the data source. Suggestions for further amendments or supplementary information can be sent to [email protected].

Research Keywords

  • Fuzzy clustering algorithms
  • Powerformer
  • Stator single-phase-to-ground fault