Skip to main navigation Skip to search Skip to main content

Novel demand-controlled optimization of constant-air-volume mechanical ventilation for indoor air quality, durability and energy saving

  • Sheng Zhang
  • , Zhengtao Ai*
  • , Zhang Lin*
  • *Corresponding author for this work

    Research output: Journal Publications and Reviews › RGC 21 - Publication in refereed journal › peer-review

    Abstract

    Demand-controlled ventilation (DCV) is widely used for the energy-efficient provision of indoor air quality. However, existing DCV requires a continuously variable airflow rate, and is not applicable to the constant-air-volume mechanical ventilation (generally in buildings with room air conditioners and free-running buildings). This study proposes a novel DCV for constant-air-volume mechanical ventilation. To achieve high ventilation efficiency, the proposed DCV operates the constant-air-volume mechanical ventilation continuously and intermittently at full-load/quasi-full-load and partial-load conditions respectively, which is controlled by the upper and lower concentration limits of indoor airborne pollutants (indicated by indoor CO2 concentration). The larger upper and lower concentration limits are preferred for energy saving, but could deteriorate indoor air quality, and cause durability problems due to frequent on-off operations. A genetic algorithm-based optimization is developed to determine the upper and lower concentration limits to maximize energy efficiency while satisfying the demand on indoor air quality and avoiding excessively frequent on-off operations. Case studies verify that the ventilation performance of the proposed DCV optimization is more sensitive to the lower concentration limit than the upper concentration limit. The conventional methods (the continuous ventilation and the intermittent ventilation) for the constant-air-volume mechanical ventilation risk low energy efficiency and deteriorated durability. The proposed DCV optimization improves energy efficiency by up to 88% while meeting demanded indoor air quality and durability.
    Original languageEnglish
    Article number116954
    JournalApplied Energy
    Volume293
    Online published23 Apr 2021
    DOIs
    Publication statusPublished - 1 Jul 2021

    UN SDGs

    This output contributes to the following UN Sustainable Development Goals (SDGs)

    1. SDG 7 - Affordable and Clean Energy
      SDG 7 Affordable and Clean Energy

    Research Keywords

    • Constant-air-volume
    • Continuous operation
    • Demand-controlled ventilation
    • Intermittent operation
    • Pollutant concentration limits

    RGC Funding Information

    • RGC-funded

    Fingerprint

    Dive into the research topics of 'Novel demand-controlled optimization of constant-air-volume mechanical ventilation for indoor air quality, durability and energy saving'. Together they form a unique fingerprint.

    Cite this