TY - GEN
T1 - Fast transient control of single-phase dynamic voltage restorer (DVR) without external DC source
AU - Ho, Carl N.M.
AU - Chung, Henry S.H.
PY - 2006
Y1 - 2006
N2 - This paper presents a fast dynamic control scheme for the capacitor-supported single-phase dynamic voltage restorer (DVR). The scheme consists of two main control loops as inner and outer control loops. The inner loop is used to dictate the gate signals for the switches in the DVR. It is based on the boundary control method with the second-order switching surface. The load voltage can ideally be reverted to the steady state in two switching actions during a supply voltage dip. The outer loop is used to generate the DVR output reference for the first loop. It has three control modes for achieving two different functions, including output regulation and output restoration. The first mode is for regulating the capacitor voltage on the dc side of the inverter, so that the output of the DVR is regulated at the nominal voltage. The second mode is for restoring the output with the near minimum energy injection by the DVR during a voltage dip. The third mode serves for the same purpose as the second mode. However, it will be activated when the capacitor voltage is reduced to a level that starts distorting the output voltage. The mode boundaries will be derived in this paper. By studying the small-signal characteristics of the control loops, a set of design procedures will be derived. A 500VA, 110V, 60Hz prototype has been built and tested with nonlinear loads. The dynamic behaviors of the prototype under different voltage dip depths will be investigated.
AB - This paper presents a fast dynamic control scheme for the capacitor-supported single-phase dynamic voltage restorer (DVR). The scheme consists of two main control loops as inner and outer control loops. The inner loop is used to dictate the gate signals for the switches in the DVR. It is based on the boundary control method with the second-order switching surface. The load voltage can ideally be reverted to the steady state in two switching actions during a supply voltage dip. The outer loop is used to generate the DVR output reference for the first loop. It has three control modes for achieving two different functions, including output regulation and output restoration. The first mode is for regulating the capacitor voltage on the dc side of the inverter, so that the output of the DVR is regulated at the nominal voltage. The second mode is for restoring the output with the near minimum energy injection by the DVR during a voltage dip. The third mode serves for the same purpose as the second mode. However, it will be activated when the capacitor voltage is reduced to a level that starts distorting the output voltage. The mode boundaries will be derived in this paper. By studying the small-signal characteristics of the control loops, a set of design procedures will be derived. A 500VA, 110V, 60Hz prototype has been built and tested with nonlinear loads. The dynamic behaviors of the prototype under different voltage dip depths will be investigated.
KW - Boundary control
KW - Dynamic voltage restorer
UR - https://www.scopus.com/pages/publications/42449164673
UR - https://www.scopus.com/pages/publications/42449164673#tab=impact
U2 - 10.1109/PESC.2006.1712085
DO - 10.1109/PESC.2006.1712085
M3 - RGC 32 - Refereed conference paper (with host publication)
SN - 0780397169
SN - 9780780397163
BT - PESC Record - IEEE Annual Power Electronics Specialists Conference
T2 - 37th IEEE Power Electronics Specialists Conference 2006, PESC'06
Y2 - 18 June 2006 through 22 June 2006
ER -