N2 - Background: The shortage of isolation facilities in hospitals was highlighted during the severe acute respiratory syndrome (SARS) pandemic in 2003. Yet, as the nature and scale of future pandemics cannot be adequately estimated, it is difficult to justify construction of sufficient isolation facilities. A fast-track and cost-effective ventilation strategy for the retrofitting of existing general wards could help hospitals deal with patient surges. Aim: This article reviews the effectiveness of a fast-track, makeshift isolation approach employed during the SARS outbreak which involved installing simple window-mounted exhaust fans to create negative-pressure airflow in hospital general wards. Methods: Computational fluid dynamics (CFD) was used to assess by simulation whether the approach adopted meets US Centers for Disease and Control and Prevention requirements for properly constructed isolation wards. Findings: CFD simulation revealed that this makeshift approach could match the ventilation standards of isolation rooms. The approach was certainly effective as no secondary infections were reported in hospitals that used it during SARS. Conclusions: When there is a shortfall in isolation facilities to accommodate a surge in patients, the proposed ventilation set-up could be quickly and widely implemented by existing general wards. © 2012 The Healthcare Infection Society.
AB - Background: The shortage of isolation facilities in hospitals was highlighted during the severe acute respiratory syndrome (SARS) pandemic in 2003. Yet, as the nature and scale of future pandemics cannot be adequately estimated, it is difficult to justify construction of sufficient isolation facilities. A fast-track and cost-effective ventilation strategy for the retrofitting of existing general wards could help hospitals deal with patient surges. Aim: This article reviews the effectiveness of a fast-track, makeshift isolation approach employed during the SARS outbreak which involved installing simple window-mounted exhaust fans to create negative-pressure airflow in hospital general wards. Methods: Computational fluid dynamics (CFD) was used to assess by simulation whether the approach adopted meets US Centers for Disease and Control and Prevention requirements for properly constructed isolation wards. Findings: CFD simulation revealed that this makeshift approach could match the ventilation standards of isolation rooms. The approach was certainly effective as no secondary infections were reported in hospitals that used it during SARS. Conclusions: When there is a shortfall in isolation facilities to accommodate a surge in patients, the proposed ventilation set-up could be quickly and widely implemented by existing general wards. © 2012 The Healthcare Infection Society.
KW - Air ventilation
KW - Computational fluid dynamics
KW - Infection control
KW - Pandemic
KW - Severe acute respiratory syndrome
KW - Surge capacity
UR - http://www.scopus.com/inward/record.url?scp=84863867567&partnerID=8YFLogxK
UR - https://www.scopus.com/record/pubmetrics.uri?eid=2-s2.0-84863867567&origin=recordpage
U2 - 10.1016/j.jhin.2012.04.013
DO - 10.1016/j.jhin.2012.04.013
M3 - RGC 21 - Publication in refereed journal
C2 - 22738612
SN - 0195-6701
VL - 81
SP - 246
EP - 250
JO - Journal of Hospital Infection
JF - Journal of Hospital Infection
IS - 4
ER -