Skip to main navigation Skip to search Skip to main content

Experimental investigation of thermal and ventilation performances of stratum ventilation

    Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review

    Abstract

    Stratum ventilation has been proposed to cope for elevated indoor temperatures. Air speed, temperature and CO2 concentration of a stratum ventilated office are investigated experimentally. The data obtained under well defined conditions and therefore can be used for validating numerical models. Thermal comfort conditions and ventilation efficiency are studied based on the experimental results of four experimental cases. Thermal comfort indices, i.e. PMV, PPD and PD are calculated from measured data. The values of these indices are found to satisfy the requirements of ISO 7730, CR 1752-1998 and ASHRAE 55-2010. In terms of thermal comfort, the two cases with supply air temperature of 21 °C are found to perform better compared with the two cases with supply air temperature of 19 °C. For all the cases, the ventilation effectiveness is close to 1.5. This ventilation method could therefore be expected to provide indoor air quality in an efficient way. © 2011 Elsevier Ltd.
    Original languageEnglish
    Pages (from-to)1309-1320
    JournalBuilding and Environment
    Volume46
    Issue number6
    DOIs
    Publication statusPublished - Jun 2011

    UN SDGs

    This output contributes to the following UN Sustainable Development Goals (SDGs)

    1. SDG 7 - Affordable and Clean Energy
      SDG 7 Affordable and Clean Energy
    2. SDG 9 - Industry, Innovation, and Infrastructure
      SDG 9 Industry, Innovation, and Infrastructure
    3. SDG 12 - Responsible Consumption and Production
      SDG 12 Responsible Consumption and Production

    Research Keywords

    • Elevated room temperature
    • Indoor air quality
    • Stratum ventilation
    • Thermal comfort
    • Ventilation effectiveness

    Fingerprint

    Dive into the research topics of 'Experimental investigation of thermal and ventilation performances of stratum ventilation'. Together they form a unique fingerprint.