Abstract
Thermal sensation is studied experimentally under mixing ventilation, displacement ventilation, and stratum ventilation in an environmental chamber. Forty-eight subjects participated in all tests under the same boundary conditions but different ventilation methods in the classroom. Thermal comfort analysis was carried out according to the designated supply airflow rate, room temperature, and relative humidity for the three ventilation methods. The thermal neutral temperature under stratum ventilation is approximately 2.5°C higher than that under mixing ventilation and 2.0°C higher than that under displacement ventilation. This result indicates that stratum ventilation could provide satisfactory thermal comfort level to rooms of temperature up to 27°C. The energy saving attributable to less ventilation load alone is around 12% compared with mixing ventilation and 9% compared with displacement ventilation. © 2011 John Wiley & Sons A/S.
| Original language | English |
|---|---|
| Pages (from-to) | 231-239 |
| Journal | Indoor Air |
| Volume | 21 |
| Issue number | 3 |
| DOIs | |
| Publication status | Published - Jun 2011 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Research Keywords
- Comfort
- Elevated room temperature
- Energy-saving potential
- Human subject test
- Stratum ventilation
- Thermal neutral temperature