Effects of Imbalances and Nonlinear Loads on the Voltage Balance of a Neutral-Point-Clamped Inverter

  • J. Pou
  • , D. Boroyevich
  • , R. Pindado

Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review

Abstract

The effects of linear imbalances and nonlinear loads on the voltage balance of the neutral-point-clamped converter are described in this paper. The study reveals that a negative sequence of output currents (linear imbalance) may produce additional low-frequency oscillations to the neutral-point voltage. Similar consequences are produced by odd-order current harmonics from a nonlinear load, while even-order harmonics can cause the neutral-point voltage to shift. Furthermore, the second, fourth, and eighth output current harmonics might produce instability to the neutral-point voltage. The second and fourth harmonics are the worst components. The maximum amplitudes of these harmonics superposed to the current fundamentals that the system can tolerate are described. Simulated and experimental examples are presented. © 2005 IEEE.
Original languageEnglish
Pages (from-to)123-131
JournalIEEE Transactions on Power Electronics
Volume20
Issue number1
DOIs
Publication statusPublished - Jan 2005
Externally publishedYes

Bibliographical note

Publication details (e.g. title, author(s), publication statuses and dates) are captured on an “AS IS” and “AS AVAILABLE” basis at the time of record harvesting from the data source. Suggestions for further amendments or supplementary information can be sent to [email protected].

Research Keywords

  • Linear imbalances
  • Nearest vectors
  • Neutral-point balance
  • Nonlinear loads
  • Space-vector modulation
  • Three-level inverter