Abstract
The effects of linear imbalances and nonlinear loads on the voltage balance of the neutral-point-clamped converter are described in this paper. The study reveals that a negative sequence of output currents (linear imbalance) may produce additional low-frequency oscillations to the neutral-point voltage. Similar consequences are produced by odd-order current harmonics from a nonlinear load, while even-order harmonics can cause the neutral-point voltage to shift. Furthermore, the second, fourth, and eighth output current harmonics might produce instability to the neutral-point voltage. The second and fourth harmonics are the worst components. The maximum amplitudes of these harmonics superposed to the current fundamentals that the system can tolerate are described. Simulated and experimental examples are presented. © 2005 IEEE.
| Original language | English |
|---|---|
| Pages (from-to) | 123-131 |
| Journal | IEEE Transactions on Power Electronics |
| Volume | 20 |
| Issue number | 1 |
| DOIs | |
| Publication status | Published - Jan 2005 |
| Externally published | Yes |
Bibliographical note
Publication details (e.g. title, author(s), publication statuses and dates) are captured on an “AS IS” and “AS AVAILABLE” basis at the time of record harvesting from the data source. Suggestions for further amendments or supplementary information can be sent to [email protected].Research Keywords
- Linear imbalances
- Nearest vectors
- Neutral-point balance
- Nonlinear loads
- Space-vector modulation
- Three-level inverter
Fingerprint
Dive into the research topics of 'Effects of Imbalances and Nonlinear Loads on the Voltage Balance of a Neutral-Point-Clamped Inverter'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver