Development and In-situ validation of a multi-zone demand-controlled ventilation strategy using a limited number of sensors

Research output: Journal Publications and Reviews (RGC: 21, 22, 62)21_Publication in refereed journalpeer-review

38 Scopus Citations
View graph of relations

Author(s)

Detail(s)

Original languageEnglish
Pages (from-to)28-37
Journal / PublicationBuilding and Environment
Volume57
Publication statusPublished - Nov 2012
Externally publishedYes

Abstract

This paper presents a new strategy using a limited number of sensors for demand-controlled ventilation (DCV) of multi-zone office buildings. The conventional CO 2-based demand-controlled ventilation strategy for multi-zone offices requires CO 2 sensors and supply airflow meters being installed in all zones. However, in many practical cases, CO 2 sensors might not be available or not necessary. To control the outdoor airflow based on actual occupancy variations in such cases, a DCV strategy with two implementing schemes is developed for different sensor availabilities. The first scheme is used for the situation when CO 2 sensors in individual zones are not available but the airflow meters for individual zones are installed. The second scheme is used for the conditions when CO 2 sensors and airflow meters in individual zones are not available. These two schemes use two different approaches to estimate the outdoor airflow fraction of the critical zone approximately. Both schemes only require the CO 2 sensor in the main return air to dynamically detect the total occupancy number. The developed strategy is implemented and validated in a high-rise office building in Hong Kong. The site test results show that the strategy can achieve significant energy saving while maintaining acceptable IAQ in the situations where only limited sensors are available. © 2012 Elsevier Ltd.

Research Area(s)

  • Demand-controlled ventilation, Energy saving, In-situ validation, Indoor air quality, Limited sensor, Multi-zone office building