Abstract
In normal office building wiring system, the supply is three-phase four-wire system and most of the nonlinear loads are single phased such as personal computer and electronic office equipment. Rising main installation forms the skeleton of the building wiring system.
For balanced systems triplen harmonic components of current are added in the neutral conductor, other components are cancelled. In unbalanced condition triplen harmonics and other components of current flow through the neutral conductor. Therefore, a measure of neutral current is important and this will reflect an elementary impression of power quality of the wiring system. Zero sequence harmonic mitigation such as installation of filter in the neutral conductor and its location will be suggested. Moreover, this paper has also explored the third harmonic influence on neutral-earth voltage. © IEE 2002.
For balanced systems triplen harmonic components of current are added in the neutral conductor, other components are cancelled. In unbalanced condition triplen harmonics and other components of current flow through the neutral conductor. Therefore, a measure of neutral current is important and this will reflect an elementary impression of power quality of the wiring system. Zero sequence harmonic mitigation such as installation of filter in the neutral conductor and its location will be suggested. Moreover, this paper has also explored the third harmonic influence on neutral-earth voltage. © IEE 2002.
| Original language | English |
|---|---|
| Title of host publication | Fifth International Conference on Power System Management and Control |
| Publisher | Institution of Electrical Engineers (IEE) |
| Pages | 118-123 |
| ISBN (Print) | 0-85296-748-9 |
| DOIs | |
| Publication status | Published - 2002 |
| Event | 5th International Conference on Power System Management and Control - London, United Kingdom Duration: 17 Apr 2002 → 19 Apr 2002 |
Publication series
| Name | IEE Conference Publication |
|---|---|
| Number | 488 |
| ISSN (Print) | 0537-9989 |
Conference
| Conference | 5th International Conference on Power System Management and Control |
|---|---|
| Place | United Kingdom |
| City | London |
| Period | 17/04/02 → 19/04/02 |
Bibliographical note
Full text of this publication does not contain sufficient affiliation information. With consent from the author(s) concerned, the Research Unit(s) information for this record is based on the existing academic department affiliation of the author(s).Fingerprint
Dive into the research topics of 'Analysis of zero sequence passive filter harmonics mitigation device for building wiring system'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver