Analysis of zero sequence passive filter harmonics mitigation device for building wiring system

    Research output: Chapters, Conference Papers, Creative and Literary WorksRGC 32 - Refereed conference paper (with host publication)peer-review

    Abstract

    In normal office building wiring system, the supply is three-phase four-wire system and most of the nonlinear loads are single phased such as personal computer and electronic office equipment. Rising main installation forms the skeleton of the building wiring system.

    For balanced systems triplen harmonic components of current are added in the neutral conductor, other components are cancelled. In unbalanced condition triplen harmonics and other components of current flow through the neutral conductor. Therefore, a measure of neutral current is important and this will reflect an elementary impression of power quality of the wiring system. Zero sequence harmonic mitigation such as installation of filter in the neutral conductor and its location will be suggested. Moreover, this paper has also explored the third harmonic influence on neutral-earth voltage. © IEE 2002.
    Original languageEnglish
    Title of host publicationFifth International Conference on Power System Management and Control
    PublisherInstitution of Electrical Engineers (IEE)
    Pages118-123
    ISBN (Print)0-85296-748-9
    DOIs
    Publication statusPublished - 2002
    Event5th International Conference on Power System Management and Control - London, United Kingdom
    Duration: 17 Apr 200219 Apr 2002

    Publication series

    NameIEE Conference Publication
    Number488
    ISSN (Print)0537-9989

    Conference

    Conference5th International Conference on Power System Management and Control
    PlaceUnited Kingdom
    CityLondon
    Period17/04/0219/04/02

    Bibliographical note

    Full text of this publication does not contain sufficient affiliation information. With consent from the author(s) concerned, the Research Unit(s) information for this record is based on the existing academic department affiliation of the author(s).

    Fingerprint

    Dive into the research topics of 'Analysis of zero sequence passive filter harmonics mitigation device for building wiring system'. Together they form a unique fingerprint.

    Cite this