Skip to main navigation Skip to search Skip to main content

A STUDY ON THE POSSIBILITY OF THERMOELECTRIC HEATING/COOLING IN BUILDINGS

  • J. Liang
  • , Kin Yeung
  • , R.-X. Du
  • , Y.-L. Chan
  • , Jin-Yeu T.

Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review

Abstract

This paper presents a study on the use of thermoelectric heating and cooling in buildings. The system, called Smart Wall, consists of thermoelectric (TE) modules, a power supply (including a rechargeable battery and an AC power rectifier), a water circulation system, and a computer control system. Smart Wall has three functions: heating, cooling, and power generation. To improve its coefficient of performance (COP), it uses the so-called symbiotic generation to maximize the energy usage. In order to investigate the performance of Smart Wall, a theoretical model is first developed. Based on computer simulation, it is found that under a typical condition, Smart Wall can achieve a COP of 0.605 for cooling and 0.875 for heating. A small experiment model of 1.8 m × 1.2 m × 0.4 m is also built. The experiment result confirms the simulation results. Because Smart Wall is clean, quiet, and safe, if the COP can be further improved the system would have great potential in the future.
Original languageEnglish
Article number203-3524
Pages (from-to)250-259
JournalInternational Journal of Power and Energy Systems
Volume26
Issue number3
DOIs
Publication statusPublished - 2006
Externally publishedYes

Research Keywords

  • Thermoelectric cooling and heating
  • Symbiotic generation
  • Coefficient of performance (COP)

Fingerprint