A simplified explicit model for determining the performance of a chilled water cooling coil

Research output: Journal Publications and Reviews (RGC: 21, 22, 62)21_Publication in refereed journalpeer-review

8 Scopus Citations
View graph of relations

Author(s)

  • C. K. Lee

Related Research Unit(s)

Detail(s)

Original languageEnglish
Pages (from-to)167-175
Journal / PublicationInternational Journal of Refrigeration
Volume43
Publication statusPublished - Jul 2014

Abstract

A simplified explicit model for the chilled water cooling coil was presented which could determine the performance of even a partially-wet coil without any need for iterative calculations. A quadratic correlation was derived for evaluating the dry portion of a partially-wet coil from the inlet chilled water temperature based on performance data generated from a validated numerical model for a sample coil over a range of operating conditions. By applying the present explicit model to simulate the performance of the sample coil, it was found that the errors in the calculated coil total capacities did not exceed 2.2% when compared with those based on the numerical model. The percentage errors in the simulated coil latent capacities varied widely from 100% for a just-slightly-wet coil down to 0.26% for a fully-wet coil. Nevertheless, the present model was considered an efficient and yet accurate approach for determining the performance of a chilled water cooling coil. © 2014 Elsevier Ltd and IIR. All rights reserved.

Research Area(s)

  • Air-conditioning, Chilled water coil, Log-mean-enthalpy difference, Log-mean-temperature difference, Overall heat transfer value