Skip to main navigation Skip to search Skip to main content

A simplified explicit model for determining the performance of a chilled water cooling coil

  • C. K. Lee

Research output: Journal Publications and ReviewsRGC 21 - Publication in refereed journalpeer-review

Abstract

A simplified explicit model for the chilled water cooling coil was presented which could determine the performance of even a partially-wet coil without any need for iterative calculations. A quadratic correlation was derived for evaluating the dry portion of a partially-wet coil from the inlet chilled water temperature based on performance data generated from a validated numerical model for a sample coil over a range of operating conditions. By applying the present explicit model to simulate the performance of the sample coil, it was found that the errors in the calculated coil total capacities did not exceed 2.2% when compared with those based on the numerical model. The percentage errors in the simulated coil latent capacities varied widely from 100% for a just-slightly-wet coil down to 0.26% for a fully-wet coil. Nevertheless, the present model was considered an efficient and yet accurate approach for determining the performance of a chilled water cooling coil. © 2014 Elsevier Ltd and IIR. All rights reserved.
Original languageEnglish
Pages (from-to)167-175
JournalInternational Journal of Refrigeration
Volume43
DOIs
Publication statusPublished - Jul 2014

Research Keywords

  • Air-conditioning
  • Chilled water coil
  • Log-mean-enthalpy difference
  • Log-mean-temperature difference
  • Overall heat transfer value

Fingerprint

Dive into the research topics of 'A simplified explicit model for determining the performance of a chilled water cooling coil'. Together they form a unique fingerprint.

Cite this